Extruded Aluminum Model "EX" Vent
Long Specifications

Click Here to View Product

  We manufacturer several types of aluminum louvered wall ventilators for ventilating crawl spaces or crawlspaces, ceiling plenums, chimney flues, foundations, pipe spaces, and other conditions.  These ventilators are typically installed in masonry walls and include crawl space ventilators or crawlspace ventilators.  Both extruded and cast aluminum ventilators are provided.  Accessories include insect screens, ducts, dampers, and inside registers.

This guide specification section can be used to specify Model EX, an extruded aluminum wall ventilator.  Model FL, a flanged extruded aluminum wall ventilator can be specified with SECTION 10236 - EXTRUDED ALUMINUM FLANGED WALL VENTS.  Cast aluminum wall ventilators, Model C, can be specified with SECTION 10237 - CAST ALUMINUM WALL VENTS.

The specifier will need to edit this product specification for a specific project to reflect the options and applications being used.  The guide section has been written so that most editing can be accomplished by deleting unnecessary requirements.  Options are indicated by [   ].  Notes to assist the specifier in selecting options and editing the specification guide are printed in bold and indicated with.  For final editing, all brackets and notes will need to be deleted from the guide.

 

PART 1 - GENERAL

1.1 SUMMARY

  Edit the following paragraph to reflect project conditions. 

A. Section includes:  Aluminum wall ventilators with fixed louvers, [adjustable damper,] [duct extension] [inside register] and insect screens for installation in [masonry] [concrete] [_____] walls to provide ventilation for [crawl spaces] [ceiling plenums] [chimney flues] [foundations] [pipe spaces] [_____].

B. Related sections:

  List other specification sections dealing with work directly related to this section such as the following.  Typically wall ventilators are installed in clay brick or type of masonry walls.  They can also be used in concrete or other types of wall construction
1. Section 03300 - Cast-in-Place Concrete:  Concrete walls to receive extruded aluminum ventilators.

2. Section 04800 - Masonry Assemblies:  [Clay brick] [Concrete unit] masonry walls to receive extruded aluminum ventilators.

1.2 REFERENCES

  List by number and full title reference standards referred to in remainder of specification section.  Delete non-applicable references. 

A. American Architectural Manufacturers Association (AAMA):
1. AAMA 605.2 - Voluntary Specification for High Performance Organic Coatings on Architectural Extrusions and Panels.

2. AAMA 606.1 - Voluntary Guide Specification and Inspection Methods for Integral Color Anodic Finishes for Architectural Aluminum.

3. AAMA 607.1 - Voluntary Guide Specification and Inspection Methods for Clear Anodic Finishes for Architectural Aluminum.

B. American Society for Testing and Materials (ASTM) Publications:
1. ASTM B209 - Aluminum and Aluminum-Alloy Sheet and Plate.

2. ASTM B221 - Aluminum-Alloy Extruded Bar, Rod, Wire, Shape, and Tube.

1.3 SUBMITTALS
A. Provide in accordance with Section 01330 - Submittal Procedures:
1. Product data for wall ventilators.

2. Shop drawings showing construction, dimensions, and installation details.

3. Sample of finish.

PART 2 - PRODUCTS

2.1 ACCEPTABLE MANUFACTURERS

A. Manufacturers of equivalent products submitted and approved in accordance with Section 01630 - Product Substitution Procedures.
2.2 MATERIALS
A. Extruded aluminum:  [0.125 inch] [3 mm] minimum thickness extruded aluminum complying with ASTM B221, Alloy 6063, Temper T-5.

B. Sheet aluminum:  [0.063 inch] [16 mm] minimum thickness sheet aluminum sheet complying with ASTM B209 6063, Temper T-6.

C. Fasteners:  Type, size, and spacing as recommended by ventilator manufacturer for project conditions.

  Include the following paragraph if ventilators are to be installed with sealant. 
D. Sealant:  Type as [specified in Section 07900 - Joint Sealers.] [recommended by ventilator manufacturer.]
2.3 WALL VENTS
A. Type:  Extruded aluminum wall ventilator with insect screen [opposed blade adjustable damper] [duct extension] [and] [inside register]; Model EX.
  We provides ventilators in stock sizes ranging from 8-1/8 by 2-3/8 inches (206 by 60 mm) to 48 by 7-3/4 inches (1219 by 197 mm).  Refer to product literature for available stock sizes.  Extruded ventilators can be custom fabricated to other heights and any width to 8 feet (2438 mm) without exposed mullions.  Depth of extruded aluminum ventilators without flanges is 4 inches (102 mm).  Some extruded ventilators are load bearing depending on size. 
B. Nominal size:  [4 inches] [102 mm] deep by [_____] [inches] [mm] wide by [_____] [inches] [mm] high.
C. Construction:  Framed ventilator without flanges and with overlapping horizontal louver blades fabricated from extruded aluminum sections.
1. Louver blades:  Fixed, horizontal blades [1 inch] [25 mm] deep set at 45 degrees at [1 inch] [25 mm] on center.  Top of blade formed with storm drip.

2. Top frame:  Extruded member with mortar ribs and front drip edge.

3. Bottom frame:  Extruded member with mortar ribs, back water stop, and front drip edge.

4. Connections:  Fabricate ventilators with mechanical connections such that all fasteners are concealed when ventilator is installed.

D. Insect screen:  18 by 14 mesh aluminum screen set behind louvers in extruded stop on frame.
2.4 ACCESSORIES

Model EX ventilators can be equipped with opposed blade damper.  Include this paragraph if dampers are required.

A. Dampers:  Equip wall ventilators with opposed vertical blade damper set behind horizontal fixed louver blades and operable from exterior with screwdriver.  Provide cutout in bottom louver blade for screwdriver adjustment of damper.
Model EX ventilators can be supplied with straight aluminum rectangular duct extension to accommodate thickness of wall in which ventilator is installed.  Include the following paragraphs if duct extensions are required. 
B. Duct extension:  Provide wall ventilators with straight, rectangular duct extension to attach to ventilator and extend through wall.
1. Fabricate from sheet aluminum and securely attach to ventilator with fasteners of type, size, and spacing as recommended by manufacturer.
  Width of duct will be 1/4 inch (6 mm) greater than ventilator width and 1/8 inch (3 mm) greater than ventilator height.  Length of duct extension will vary with thickness of wall and project conditions.  Length may be specified in this section or dimensioned on Drawings.  To eliminate potential conflicts, length should not be indicated in both locations. 
2. Size:  Width and height to accommodate ventilator size by [[_____] [inches] [mm]] long.] [length required to penetrate wall.] [length indicated on Drawings and approved shop drawings.]
Model EX wall ventilator can be supplied with an optional inside aluminum register.  Registers are not attached directly to ventilators but are shipped loose for field attachment.  Depending of project conditions, registers may be attached to duct extensions or installed to interior wall face.  Include the following paragraph if inside registers are required. 
C. Inside registers:  Provide wall ventilators with inside register to be field attached to [duct extensions] [inside face of wall].
1. Type:  Aluminum register with individual adjustable vanes and multi-blade damper.

2. Size:  Width and height to accommodate ventilator size.

2.5 FACTORY FINISH

  Standard finish for extruded aluminum wall ventilators is a clear anodized finish.  As an option, medium and dark bronze anodized, thermoset (baked enamel), and Kynar finishes are available. 

A. Wall ventilator finish:  Factory applied [clear anodized coating complying with AAMA 607.1 - MM10C22A31.]  [[medium] [dark] bronze anodized coating complying with AAMA 606.1 - MM10C22A44.]  [fluoropolymer Kynar colored paint coating complying with AAMA 605.2.] [thermoset polyester enamel.]
  Include the following paragraph if a either Kynar or thermoset enamel finish is being specified.  Refer to product literature for available colors or contact Industries regarding custom colors. 
B. Color:  [_____] [As selected by Architect from manufacturer's standard range] [Custom color as designated by Architect].
  Include the following paragraph if duct extensions are being specified. 
C. Duct extension finish:  Mill finished aluminum.

PART 3 - EXECUTION

3.1 COORDINATION

  Depending on size, some extruded aluminum wall ventilators are load bearing.  Other sizes may require supplementary framing or lintels.  Contact Industries for loading bearing capacities of extruded ventilators. 

A. Coordinate supply of ventilators with construction of walls to ensure proper sizing and placement of ventilator openings.  [Ensure that adequate framing and lintels are installed in accordance with [Section 05100 - Structural Metal Framing] [_____].
  Typically extruded aluminum wall ventilators are built into wall with mortar as clay brick or other type of masonry is laid. 
B. Coordinate provision of wall ventilators with construction of masonry walls.  Deliver ventilators to site in time to allow building into masonry wall and to avoid delays.
3.2 INSTALLATION
A. Install ventilators, [dampers,] [duct extensions,] [and] [inside registers] in accordance with manufacturer's installation instructions and approved shop drawings.

B. Do not installed bent, scratched, or otherwise damaged ventilators.  Remove damaged components from site and replace.

C. Install ventilators secure, level, plumb, and flush with wall surface.

  Include the following threeparagraphs if ventilators are to be built into masonry walls. 
D. Build ventilators into wall with mortar as part of masonry construction specified in Section [04800 - Masonry Assemblies] [_____].

E. Exercise care that wet mortar is not splashed onto aluminum ventilator during installation.

F. For ventilators greater than [30 inches] [762 mm] wide:  Do not mortar jambs.  Install with sealant and backer rod [as specified in Section 07900 - Joint Sealers].

  Include the following paragraphs if ventilators are to be installed in rough openings after wall is constructed. 
G. Install ventilators in wall openings after walls are constructed in accordance with Drawing details and approved shop drawings.
1. Secure ventilators with clips attached to rear of ventilator and anchored to perimeter of wall opening.

2. Seal around entire perimeter of ventilator with sealant and backer rod [as specified in Section 07900 - Joint Sealers].

3.3 CLEANING
A. Exercise care in removing mortar and cementitious materials from aluminum ventilators in order to avoid scratching.  Splashed mortar or cement plaster shall be cleaned from ventilator with dry burlap wipe.  Remove after material becomes hard enough not to smear but prior to set.

B. Remove excess sealant by moderate use of mineral spirits or other solventilator acceptable to sealant manufacturer.

C. Wash exposed surfaces with solution of mild detergent applied with soft cloth.  Take care to remove dirt from corners.  Wipe surfaces clean.

 



Empire Ventilation Equipment Co., Inc. - Est. 1933

35-39 Vernon Boulevard, Long Island City, NY 11106  |   All of our products are proudly MADE IN THE USA

About Us   |    Contact Us   |    Log-In   |    View Shopping Cart

Accessories Bases Louvers Ventilators / Spring Registers / Fans
1/2“ Mesh Screens
Insect Screens
Dampers For Syphon/Eveco
Dampers For Turbine Ventilators
Adjustable Bases
Economy Bases
Standard Mounting Bases
• Flat Bases
• Ridge Roof Bases
• Curb Bases
• Slope Roof Base
Cast Aluminum Ventilators
Extruded Aluminum Ventilators
Flange Extruded Ventilators
Flush-Flange Louvers
Roof Louvers
Soffets
Strip Ventilators
Eveco Ventilators
Insul-Ventilators
Syphon Ventilators
Turbine Ventilators
Booster Fans
Spring Register

© Copyright 2014. Empire Ventilation Equipment Co., Inc. All Rights Reserved. Site Designed and Maintained by Rapport Associates, Ltd.

Eveco Ventilators
Insul-Ventilators
Syphon Ventilators
Turbine Ventilators
1/2“ Mesh Screens
Insect Screens
Dampers For Syphon or Eveco
Dampers For Turbine Ventilators
Adjustable Bases
Economy Bases
Standard Mounting Bases
• Flat Bases
• Ridge Roof Bases
• Curb Bases
• Slope Roof Base
Booster Fans
Cast Aluminum Ventilators
Extruded Aluminum Ventilators
Flange Extruded Ventilators
Flush-Flange Louvers
Roof Louvers
Soffets
Strip Ventilators
Spring Register
Repair Kit
About Us    |    Pressroom    |    Contact    |    Building Codes   |    Blog
Home    |    Log In    |    Shopping Cart