Ventilation Building Codes

Disclaimer: The Information contained on this web page has been collected and presented as a guide.  It should be used as a guide only and should not be relied upon as the sole source of information relating to ventilation requirements or legal requirements in any state or municipality. No warranty, either express or implied, is made with respect to the information contained herein. For additional information contact the specific state or municipality to obtain specific technical or legal ventilating requirements that may apply. Empire Ventilation Equipment Co., Inc. is not responsible for any loss, inconvenience, damage (whether special or consequential) or claims arising out of the use of the information contained on this page.


Virginia

R303.9 Insect screens. Every door, window and other outside opening required for ventilation purposes shall be supplied with approved tightly fitted screens of not less than 16 mesh per inch (16 mesh per 25 mm) and every screen door used for insect control shall have a self-closing device.

403.1 Ventilation system. Mechanical ventilation shall be provided by a method of supply air and return or exhaust air. The amount of supply air shall be approximately equal to the amount of return and exhaust air. The system shall not be prohibited from producing negative or positive pressure. The system to convey ventilation air shall be designed and installed in accordance with Chapter 6.
403.2 Outdoor air required. The minimum outdoor airflow rate shall be determined in accordance with Section 403.3. Ventilation supply systems shall be designed to deliver the required rate of outdoor airflow to the breathing zone within each occupiable space.

Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding that obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design.


403.2.1 Recirculation of air. The outdoor air required by Section 403.3 shall not be recirculated. Air in excess of that required by Section 403.3 shall not be prohibited from being recirculated as a component of supply air to building spaces, except that:
1. Ventilation air shall not be recirculated from one dwelling to another or to dissimilar occupancies.
2. Supply air to a swimming pool and associated deck areas shall not be recirculated unless such air is dehumidified to maintain the relative humidity of the area at 60 percent or less. Air from this area shall not be recirculated to other spaces where 10 percent or more of the resulting supply airstream consists of air recirculated from these spaces.
3. Where mechanical exhaust is required by Note b in Table 403.3, recirculation of air from such spaces shall be prohibited. All air supplied to such spaces shall be exhausted, including any air in excess of that required by Table 403.3.
4. Where mechanical exhaust is required by Note h in Table 403.3, mechanical exhaust is required and recirculation is prohibited where 10 percent or more of the resulting supply airstream consists of air recirculated from these spaces.

403.2.2 Transfer air. Except where recirculation from such spaces is prohibited by Table 403.3, air transferred from occupiable spaces is not prohibited from serving as makeup air for required exhaust systems in such spaces as kitchens, baths, toilet rooms, elevators and smoking lounges. The amount of transfer air and exhaust air shall be sufficient to provide the flow rates as specified in Section 403.3. The required outdoor airflow rates specified in Table 403.3 shall be introduced directly into such spaces or into the occupied spaces from which air is transferred or a combination of both.

403.4 Exhaust Ventilation. Exhaust airflow rate shall be provided in accordance with the requirements in Table 403.3. Exhaust makeup air shall be permitted to be any combination of outdoor air, recirculated air and transfer air, except as limited in accordance with Section 403.2.




 


 

 




Empire Ventilation Equipment Co., Inc. - Est. 1933

35-39 Vernon Boulevard, Long Island City, NY 11106  |   All of our products are proudly MADE IN THE USA

About Us   |    Contact Us   |    Log-In   |    View Shopping Cart

Accessories Bases Louvers Ventilators / Spring Registers / Fans
1/2“ Mesh Screens
Insect Screens
Dampers For Syphon/Eveco
Dampers For Turbine Ventilators
Adjustable Bases
Economy Bases
Standard Mounting Bases
• Flat Bases
• Ridge Roof Bases
• Curb Bases
• Slope Roof Base
Cast Aluminum Ventilators
Extruded Aluminum Ventilators
Flange Extruded Ventilators
Flush-Flange Louvers
Roof Louvers
Soffets
Strip Ventilators
Eveco Ventilators
Insul-Ventilators
Syphon Ventilators
Turbine Ventilators
Booster Fans
Spring Register

© Copyright 2014. Empire Ventilation Equipment Co., Inc. All Rights Reserved. Site Designed and Maintained by Rapport Associates, Ltd.

Eveco Ventilators
Insul-Ventilators
Syphon Ventilators
Turbine Ventilators
1/2“ Mesh Screens
Insect Screens
Dampers For Syphon or Eveco
Dampers For Turbine Ventilators
Adjustable Bases
Economy Bases
Standard Mounting Bases
• Flat Bases
• Ridge Roof Bases
• Curb Bases
• Slope Roof Base
Booster Fans
Cast Aluminum Ventilators
Extruded Aluminum Ventilators
Flange Extruded Ventilators
Flush-Flange Louvers
Roof Louvers
Soffets
Strip Ventilators
Spring Register
Repair Kit
About Us    |    Pressroom    |    Contact    |    Building Codes   |    Blog
Home    |    Log In    |    Shopping Cart